Description
Structural Features
This product support type structure, it is epoxy resin cast with totally-enclosed. Anti-pollution and moisture-proof, it is suitable for moist and topic zone, the secondary windings with one measurement class and one protection class(or two), it adopts an import core with strict heat treatment.it installs the shield at the secondary outlet terminal, installed at any direction and position easily. The face and side face of shield has one hole which is used for the secondary connection, It could elicit the secondary connection at the three directions, and the shield could prevent someone from stealing the power electricity.
Technical Parameters
- Rated insulation level 12/42/75kV;
- Power factor of load: COSф=0.8(lagging);
- Rated secondary current 5A or 1A;
- Anti-Pollution: II Class;
- Standard: GBI 208-2006;
- Meter protection coefficient: FS≤10;
- Other technical parameters refer to the datum of the table.